Jefferson Davis Parish Just Adopted Its Data Center Rules. The Chicot Aquifer Is Off Limits for Primary Cooling.

Adopted 9–0 on November 10, Ordinance No. 2494 bars data centers from using potable aquifers—including the Chicot Aquifer—for primary cooling, caps property-line noise at 60 dBA, and requires a teardown bond, while leaving setback waivers open.
Jefferson Davis Parish Just Adopted Its Data Center Rules. The Chicot Aquifer Is Off Limits for Primary Cooling.
Generic photo of a data center server room (Pexels, panumas nikhomkhai). Not the site in Jefferson Davis Parish.

337.NEWS | November 23, 2026

While neighboring parishes debate moratoriums and air permits, Jefferson Davis Parish has quietly written a comprehensive data-center rulebook into parish law—and drawn a hard legal line around Southwest Louisiana's primary drinking-water supply.

On November 10, 2026, the Jefferson Davis Parish Police Jury voted 9–0 (with three jurors absent) to adopt Ordinance No. 2494, establishing parishwide siting, water, noise, road, and decommissioning standards for commercial data centers. Signed by Police Jury President Butch LaFargue and Secretary-Treasurer Dodie Huval Richie, the full text was published as Louisiana Public Notice #664420 in the Jennings Daily News on November 18 at a legal-notice cost of $240.28.

The ordinance deserves a closer look, particularly the provisions governing groundwater, noise and the Police Jury’s authority to adjust setbacks.

Which projects trigger the law

Under Section 2 and Exhibit A, the ordinance applies to any new, expanded, or materially modified facility in Jefferson Davis Parish that meets any of four thresholds:

  • 25,000 square feet or more of gross floor area devoted primarily to servers, data processing, AI computing, cryptocurrency/blockchain equipment, or related infrastructure;
  • 5 megawatts or greater in anticipated electrical demand;
  • 5 megawatts or more of installed backup or emergency generation capacity; or
  • A phased or unified project across multiple buildings, parcels, or entities under common control that meets those thresholds when combined.

Subsection (d)(6)c explicitly bars developers from splitting a campus into separate parcels, phases, or shell entities to stay underneath the 25,000-square-foot or 5-megawatt trigger.

The Chicot Aquifer ban and utility-cost rules

The sharpest provision sits in subsection (g)(8)b under Water and Wastewater:

"Water drawn from potable water aquifers, including the Chicot Aquifer, shall not be permitted as the primary source of water for continuous cooling or similar industrial processes."

Applicants must submit a detailed water-use report (Sec. (h)(3)n) disclosing maximum daily and annual water demand, cooling-system architecture, consumptive loss, and potential impacts on public water systems, groundwater, and fire flow. Once operating, owners must file an annual report (Sec. (d)(5)b) recording annual water consumption, wastewater discharge, maximum electrical demand, generator operating hours, spills or fires, and resident complaints.

On the power grid, subsection (g)(10)a requires the permittee to mitigate impacts on public electric utility systems, including paying for utility upgrades reasonably necessary to serve the campus or prevent adverse impacts on existing ratepayers.

Noise, 500-foot setbacks—and the variance clause in the fine print

Over the weekend, 337.NEWS examined what sound and wildlife research says about the 500-foot data-center setback Beauregard Parish is weighing before its temporary moratorium expires at the end of 2026.

Jefferson Davis Parish wrote four baseline buffers into subsection (g)(1):

  • 500 feet minimum between data-center buildings or major mechanical equipment and any existing occupied structure (homes, schools, businesses, clinics, or churches);
  • 300 feet minimum from any exterior property line for backup generators, cooling towers, chillers, transformers, substations, mechanical yards, and fuel storage;
  • 100 feet minimum from exterior property lines and public road rights-of-way for data-center buildings; and
  • 55 feet maximum building height unless the Police Jury approves taller structures.

Exterior noise is capped at 60 dBA at the property line, measured under ASTM E1014, with routine backup-generator testing restricted to Monday through Friday between 8:00 a.m. and 6:00 p.m., excluding legal holidays (Sec. (g)(6)).

Residents reading the setback numbers should also read subsection (g)(1)e. That clause states that the Police Jury "may increase or decrease a setback based upon site conditions, ownership agreements, noise studies, existing land uses, emergency-response needs, or mitigation measures." In practice, 500 feet and 300 feet are starting defaults, not unwaivable floors, if a developer brings neighbor agreements or an acoustic study to the jury.

Upfront fees and mandatory decommissioning bonds

As 337.NEWS reported earlier today, institutional lenders have started pricing long-term stranded-asset risk into AI data-center debt. Jefferson Davis Parish addressed local abandonment risk directly in subsection (e)(1):

  • Decommissioning bond before construction: Before permits take effect, the owner must record a signed, notarized decommissioning plan with the clerk of court and post a bond, irrevocable letter of credit, or escrow equal to a Louisiana-licensed professional engineer's full teardown and remediation estimate—updated at least every five years.
  • One-year abandonment trigger: If a facility ceases operating for one continuous year, decommissioning must start within 90 days and finish within 18 months.
  • Full review reimbursement plus 10%: Beyond a nonrefundable $60-per-acre application fee ($7,500 minimum), the developer must reimburse 100% of the parish's consulting engineering, technical, and legal review expenses plus a 10% parish handling fee before any permit or utility notice to proceed is issued (Sec. (h)(7)). Ownership transfers carry a $2,500 fee and require Police Jury approval.

Nothing in the ordinance approves a specific campus or grants a tax break; subsection (h)(5)b specifies that meeting the technical code does not obligate the Police Jury to approve a cooperative endeavor agreement or property-tax exemption. What Ordinance No. 2494 does establish is that any developer eyeing the I-10 corridor through Jennings and Welsh will face water-use restrictions, technical-review costs and decommissioning security requirements before construction.